Crowcon Xgard Bright, newest fixed gas detector with MPS sensor

17,980,000

crowcon_logo

Description

Xgard Bright: now available with MPS technology

Brand

Crowcon

Crowcon gas detectors (portable and fixed) are suitable for applications in many industries and for detecting a wide variety of dangerous gases – protecting people and plant from gas risks (toxic and flammable) in both industrial and hazardous areas with IECEx and ATEX certification. Portable product range: Gas-Pro, Gas-Pro IR, Gas-Pro PID, Gas-Pro TK, T4, Tetra 3, Gasman, Clip SGD, Detective+, Detective Wireless, LaserMethane Mini, Triple Plus+ Fixed product range: XgardIQ, IRmax, Xgard Bright, Xgard, TXgard-IS+, Flamgard Plus, TXgard Plus, Open Path Gas Detectors, FGard IR3 Flame Detector, Xsafe, F-Gas Detector
crowcon_logo

Specification

Specifications

Size 156 x 166 x 109mm (6.1 x 6.5 x 4.3inch)
Cable Entry 2x M20 (stopping plug fitted to left-side entry)
Power 10-30Vdc. 3W max
Electrical Output 4-20mA current sink or source
RS-485 Modbus RTU
HART (Optional)
Weight Aluminium alloy 1kg (2.2lbs)
Enclosure Material ADC 12 aluminium alloy
Relay Alarm 1, Alarm 2, FaultSPST contacts rated 1A 30Vdc
Sounder Out 24Vdc (nominally), 250mA maximum load
Operating Temperature -40°C to +70°C (-40°F to 158°F)Note: sensor operating temperatures vary widely.

Refer to the sensor module datasheet or contact

Crowcon for specific sensor data.

Humidity 0 to 95% RH, non-condensing
Repeatability +/- 2% FSD
Zero drift +/- 2% FSD per year maximum
Ingress protection IP65 (IP66 with weatherproof cap)
Approvals ATEX and IECExEx II 2 G Ex db IIC T6 GbEx tb IIIC T80ᶜ Db

II 2 G Ex db IIC T6 Gb

II 2 D Ex tb IIIC T80ᶜ Db

Certificate numbers:

TUV 16 ATEX 7908 X

IECEx TUR16.0035 X

EMC Compliance EN50270: 2015
Standards EN60079-0 :2012 + A11:2013
EN60079-1 :2014
IEC60079-0 :2011 Edition 6
IEC60079-1 :2014 Edition 7
Zones Certified for use in Zone 1 and Zone 2 areas

Gases and Ranges

Gas Units Max
Range
Standard
Range
Alarm 1
level
Alarm 2
level
Temp
range °C 
MPS Flam %LEL 100 100 20 40 -40 to +75
Oxygen (O2) %Vol 30 25 19 (falling) 17 (falling) -20 to +50
Carbon Monoxide (CO) PPM 1000 250 30 200 -30 to +50
Hydrogen Sulphide (H2S) PPM 100/200 25 5 10  -30 to +50
Hydrogen (H2) %LEL 100 100 20 40 -40 to +75
Methane (CH4) %LEL 100 100 20 40 -40 to +75
Pentane (C5H12) %LEL 100 100 20 40 -40 to +75
LPG %LEL 100 100 20 40 -40 to +75
Carbon Dioxide (CO2) %VOL 0-5% 0-5% 0-2% 0-3% -20 to +50
PID (VOC) – Safe Area PPM 1000 1000 30 50 -20 to +50
Infra Red Methane (CH4) %LEL 100 100 20 40 -40 to +75
Infra Red Propane (C3H8) %LEL 100 100 20 40 -40 to +75
Ammonia (NH3) – Safe Area PPM 100 50 25 25 -20 to +40
Chlorine (CL2) – Safe Area PPM 10 5 1 3 -20 to +40
Ozone (O3) – Safe Area PPM 1 1 0.1 0.2 -20 to +40
Sulphur Dioxide (SO2) – Safe Area PPM 100 10 1 1 -30 to +50
Infra Red Butane (C4H10) %LEL 100 100 20 40 -40 to +75
Infra Red Pentane (C5H12) %LEL 100 100 20 40 -40 to +75
Infra Red LPG %LEL 100 100 20 40 -20 to +55

Download

Reviews

There are no reviews yet.

Be the first to review “Crowcon Xgard Bright, newest fixed gas detector with MPS sensor”