TGas-1031-CO2 Fixed gas detector, Explosion proof

18,500,000

Available on backorder

Description

Model Range Low alarm
setting range
High alarm
setting range
Low
alarm point
High
alarm point
TGas-1031-CO2-1 0~5%vol 1000~2500ppm 2500~5000ppm 1500ppm 2500ppm
TGas-1031-CO2-2 0~20%vol 4%~8% 8%~16% 5% 10%
TGas-1031-CO2-3 0~65%vol 13%~26% 26%~52% 15% 30%
TGas-1031-CO2-4 0~100%vol 20%~40% 40~80% 30% 50%
Parameters Characteristics
Detectable gas Flammable gases, oxygen, poisonous and harmful gases
Measurement precision ±5%F.S
Repeatability 2%
Measurement range Refer to lectotype table for details
Response time <30s(T90)
Sampling method Diffusion
Working environment Temperature: -30℃ ~ 60℃

humidity: below 85% (non condensation)

Remote control mode By the adjustment mode by infrared remote control, the detector can be adjusted without opening of cover
4 ~ 20mA

output

4~20mA output corresponding to 0 ~100%

maximum load 800 ohms

Alarm output The effective alarm is 1 point or 2 points; each alarm shall use SPDT electronic relay.

Contact rating of alarm relay:

Ohmic load: 5A@24VDC or 120VAC or 240VAC

Inductive load: 50VA

Communication Communication description: three-wire system parallel RS485 protocol, 32 points at most

Connection: Twisted pair with shield

Distance: maximum 1000m

Input voltage 24VDC±25%; power: 2W/way
Explosion-proof shell Explosion-proof grade: ExdIICT5

Protection class: IP66

Using cable ≥2.5mm2×4 screened cable line, outside diameter of cable is required to be between 6mm~9mm

TGAS-1031 China Fixed gas detector, good quality

Brand

China

Reviews

There are no reviews yet.

Be the first to review “TGas-1031-CO2 Fixed gas detector, Explosion proof”