Description
Model | Range | Low alarm setting range |
High alarm setting range |
Low alarm point |
High alarm point |
TGas-1031-CO2-1 | 0~5%vol | 1000~2500ppm | 2500~5000ppm | 1500ppm | 2500ppm |
TGas-1031-CO2-2 | 0~20%vol | 4%~8% | 8%~16% | 5% | 10% |
TGas-1031-CO2-3 | 0~65%vol | 13%~26% | 26%~52% | 15% | 30% |
TGas-1031-CO2-4 | 0~100%vol | 20%~40% | 40~80% | 30% | 50% |
Parameters | Characteristics |
Detectable gas | Flammable gases, oxygen, poisonous and harmful gases |
Measurement precision | ±5%F.S |
Repeatability | 2% |
Measurement range | Refer to lectotype table for details |
Response time | <30s(T90) |
Sampling method | Diffusion |
Working environment | Temperature: -30℃ ~ 60℃
humidity: below 85% (non condensation) |
Remote control mode | By the adjustment mode by infrared remote control, the detector can be adjusted without opening of cover |
4 ~ 20mA
output |
4~20mA output corresponding to 0 ~100%
maximum load 800 ohms |
Alarm output | The effective alarm is 1 point or 2 points; each alarm shall use SPDT electronic relay.
Contact rating of alarm relay: Ohmic load: 5A@24VDC or 120VAC or 240VAC Inductive load: 50VA |
Communication | Communication description: three-wire system parallel RS485 protocol, 32 points at most
Connection: Twisted pair with shield Distance: maximum 1000m |
Input voltage | 24VDC±25%; power: 2W/way |
Explosion-proof shell | Explosion-proof grade: ExdIICT5
Protection class: IP66 |
Using cable | ≥2.5mm2×4 screened cable line, outside diameter of cable is required to be between 6mm~9mm |